EXTRUMEX is the first national manufacturer of pipes and fittings of HDPE 4710 and 100, that is listed under FM Approvals for fire networks in class 150, 200 and 267 since 1999 in Mexico.

Standardization:

  • FM Aproved

Advantages:

  • Lightness
  • Flexibility
  • Durability
  • Impact resistence
  • Butt fusion joint
  • Fittings and accessories
  • Abrasion resistance
  • Resistance to the weather
  • Low friction coefficient
  • Compatibility with other systems
Tubram for Red Against Fire
Standard presentationC. 267C. 200C. 150
SectionsSDR 7
SDR 9
SDR 11
500 ft Coil
4”4”
48/50 ft Long
6”6”
48/50 ft Long
8”8”8”
48/50 ft Long
10”10”10”
48/50 ft Long
12”12”12”
48/50 ft Long
14”14”
48/50 ft Long
16”16”
48/50 ft Long
18”18”
48/50 ft Long
20”20”
48/50 ft Long
22"
Pipe for Fire Network

Wall Thicknesses in Millimeters
Diameter
CLASS 267
CLASS 200
CLASS 150
in.
minmaxminmaxminmax
40.5
0.55
0.41
0.45
60.73
0.03
0.6
0.67
81.22
1.37
0.95
0.04
0.78
0.87
101.52
1.7
1.18
0.05
0.97
1.08
121.81
2.02
1.4
0.05
1.15
1.28
141.54
0.06
1.26
1.41
161.76
0.07
1.44
1.62
181.98
0.08
1.62
1.82
202.2
0.09
1.8
2.02
222.42
0.09
1.98
2.22

* In case of requiring special measures and Classes please consult the plant.
Note: Thickness tolerance according to standard FM-1613.

General PropertiesPE 3608PE 4710PE 100
Density of natural resin (G / CM)
0.940-0.9470.947-0.9550.930-...
Fluency index (G / 10MIN)
0.01-0.150.01-0.150.01-0.10
Bending module (MPA)
552-758758-1103552-1103
Effort to tension (MPA)
21-2421-2421-28
Resistance to slow cracking (Hours)
100-...500-...2000-...
Hydrostatic design effort (MPA)
5.52-...6.90-...5.52-...
Content of carbon black (%)
2-32-32-3
Maximum Working Pressure

According to the Designation of Raw Material
CLASS36084710PE100
BarPsi
BarPsi
BarPsi
267
18.40266.80
23.000.00
26.70387.15
200
13.80
200.10
17.00
246.50
20.00
290.00
150
11.00
159.50
14.00
203.00
16.00
232.00
Internal Hydraulic Pressure 
to Short Period
CLASS
BarPsi
267
66.70
960.48
200
50.00
720.00
150
40.00576.00